why we use current signal 4~20mA for instruments

We use 4-20 mA signal for intrinsic safety purposes, as 4-20 mA signal is weak, it never cause fire / spark in-case of short circuit or Puncture.

why we use current signal?,most of us know, the simple reason is to prevent the losses due to voltage drop if we are transmitting the voltage signals over long distances ,the effective wire resistance could change the actual value

we use 4-20 mA because the strength of the noise signal is always less than 4 mA. by transmitting the current signal we can greatly reduce the voltage drops across the wire.

In hazardous areas where field instruments are installed and where the signal through marshaling rack is coming and going moreover this electronic signal is changed into 3-15 psi instrument air which then operates the process valves located in field the minimum range of this signal is kept 4 mA so that the operation personnel in control room may differentiate between low or no signal means 4 mA is a low signal and 0 mA is no signal(means there is some problem in connection) and we don't increase the range of that signal from 20 mA

Because current from above ranges can cause spark from short circuit due to weak insulation thus completing the fire triangle (air, fuel, ignition) the fire will erupt causing inflammable objects like ammonia, methane,Oil and Gas to explode in un-controlled manner and finally
I would like to add that 4-20 mA signal is changed to 1-5 V by using a 250 ohms resistor this volt range also cannot cause spark.
For conventional 4~20mA can use 5 KM long max.... As per recommended standard >1.5 km FF loop not recommended... HART protocol upto 3KM long max

Comments

Post a Comment

Popular posts from this blog

MODE CONDITIONING PATCH CABLE-Fiber Optics

SIL assignment